ioLogik Cellular Micro RTU Controller Click&Go Logic
4-20
IF Conditions
IF conditions are events that trigger THEN/ELSE actions. Under the IF column, you can set up to 3
conditions that must be satisfied for the actions under the THEN/ELSE column to take place. As soon as the
IF conditions are satisfied, the specified THEN/ELSE action is performed. For example, an alarm can be
activated when a door is opened. Use the pull downs to specify the conditions and units of measurement (e.g.,
DI-0=OFF).
IF conditions can be specified as follows:
IF Conditions Operators Remark
DI ON, OFF, ON to OFF, OFF to ON, Change DI-x represents the channel number
Counter =, >, <, >=, <=, Change Counter-x represents the channel number.
Max Counter Value: 4,294,967,295
AI =, >, <, >=, <= AI-x represents the number of the channel.
Max Value: Depends on the analog modes
or the result of scaling. Internal
Register(Float) can be used as the
comparison or throughput setting
controlled by remote SCADA or a
Modbus/TCP program.
Relay =, >, <, >=, <= CurRelayCNT-x represents the current relay
counts for the channel.
Max Value: 4,294,967,295
Internal Register = Reg-x represents the number of the
internal
register.
x = 00 to 23 / Trigger Value: 0 to 255
Timer TIMEOUT Timer-x, x = 00 to 23
Max value: 4,294,967,295 seconds
Schedule Time, Range and Recurrence
Expansion Module
Connection Failure
0, 1
Virtual Channel =, >, <, >=, <= VC-x represents the channel number
System Start up N/A Activate when the system is starting up at
System Start
NOTE
The following IF Conditions are only supported
by ioLogik W5300 micro RTU controllers:
Expansion Module
Connection Failure
, Virtual Channel, and System Start-up.