ioLogik Cellular Micro RTU Controller Utility: ioAdmin
3-19
Type Logic 0 Logic 1
Dry contact Close to GND open
Wet contact 0 to 3 V 10 to 30 V
In Event Counter mode, the channel accepts limit or proximity switches and counts events according to the
ON/OFF status. When “Lo to Hi” is selected, the counter value increases when the attached switch is pushed.
When “Hi to Lo” is selected, the counter value increases when the switch is pushed and released.
Counter Scaling
After configuring the DI channels to Event Counter mode, an additional “Counter Scaling” tab will show the
most recent change during the basic time unit used for the virtual channels. For example, if “Update every 5 sec”
is configured in Counter Scaling, then the “Time Interval = 1 min” setting in the virtual channel with the
operation “Accumulation” means this virtual channel will add the last 12 updates every minute from the
Counter Scaling function.