ioLogik Cellular Micro RTU Controller Click&Go Logic
4-3
Overview
The ioLogik W5300 series system eliminates the need for host computers to continually poll I/O devices for
their status. Instead, the server itself is able to monitor the status of each I/O device and take the appropriate
action when the I/O status satisfies a user-defined condition. For example, the ioLogik could be configured to
send a TCP/UDP message only when the switch attached to DI-0 is turned on. This event-based structure
results in a much improved response time and a much reduced load on the host computer’s CPU and network
bandwidth.
Cellular Micro RTU Controllers are easily configured using Moxa’s Click&Go Logic. With Click&Go Logic, you can
easily and intuitively configure when and how I/O information is transmitted over the network. Simple
IF-Then-Else statements are used to specify conditions that are required for certain actions to take place. Up
to three conditions and three actions can be combined in a rule, and you can define up to 24 rules. Supported
actions include sending SNMP traps or TCP/UDP messages to up to 10 hosts at a time.
Click&Go Function Comparison Table by Product Line
Click&Go Function ioLogik E2000 ioLogik W5300
Peer-to-Peer Yes No
Remote Action Yes No
CGI Command Yes No
Trigger Logic
IF-Then-Else rule 24 rules 24 rules
Internal Register 24 24 + 28 float points
Timer 24 24
Schedule Yes Yes
Alarms
TCP/UDP Active Message Yes Yes, Unicode support
SNMP Traps Yes Yes
E-Mail Yes Yes, Unicode support
SMS No Yes, Unicode support
Features
Click&Go Logic has the following key features:
Easy local logic control using intuitive IF-Then-Else style construction.
Up to 24 user-defined rules.
Up to 3 I/O-based conditions and 3 DO or network actions per rule.
Choice of email, TCP, UDP, SNMP trap, and SMS for active I/O messaging.
Customizable message content with dynamic fields for time, date, IP address, and more.
Up to 10 simultaneous IP destinations for TCP/UDP messaging.
Internal register function for remote output control when Click&Go is running.
Timer Delay function for timing events.
Configurable interval for time-triggered events.
NOTE
In this chapter, all the descriptions are based on the ioAdmin 3.10. Be sure to use firmware V1.3 or above for
the ioLogik W5312 series, V1.5 or above is for the ioLogik W5340 series, V1.2 or above is for
the ioLogik
W5340
-HSDPA series, and Active OPC Server V1.11 or above.