ioLogik Cellular Micro RTU Controller Utility: ioAdmin
You can control how a DO/Relay output channel acts when the network is disconnected by using the Safe
Status Settings and the Host Connection Watchdog. When the Host Connection Watchdog is enabled,
a network disconnection will activate the Safe Status Settings. The DO channel can be configured to turn on,
turn off, or commence pulse output. If the Host Connection Watchdog is not enabled, then the DO/Relay
Output channel status will remain unchanged during a network disconnection.
ATTENTION
The Host Connection Watchdog is disabled by default and must be enabled for Safe Status Settings to take
effect.
Testing DI and DO Channels
You can test each channel by opening the channel’s configuration window and selecting the Test tab.
DI TEST:
DO TEST:
Use the Test panel to see how a channel’s status affects or is affected by the attached device. For DO/Relay
Output channels, you can set the on/off status or start and stop pulse output. For DI channels, you can monitor
the attached device’s on/off status, or monitor the counter.