ioLogik Cellular Micro RTU Controller Utility: ioAdmin
3-21
In DO mode, the specifications are as follows.
Type Logic 0 (OFF) Logic 1 (ON)
DO mode open short
In Pulse Output mode, the selected digital output channel will generate a square wave as specified in the
pulse mode parameters. The low and high level widths are specified in multiples of 0.5 ms for Digital Output
(1.5 s for Relay output), with a maximum setting of 65,535. For digital output, you would enter 1000 for a width
of 500 ms. If the low width value is 5000 and the high width value is 5000, the pulse output would be a square
wave with a 5-second pulse cycle. You can specify between 1 and 4,294,967,295 pulses or enter “0” for
continuous pulse output.
When the ioLogik is first powered on, the status of each DO channel is set to “OFF” by default. This behavior can
be modified using the Power On Settings. You can set a DO channel to turn “ON” when the ioLogik is powered
on, or to commence pulse output.
Relay Count Monitoring
Two types of relay counts can be recorded in the ioLogik W5340: Total Counts and Current Counts. Relay Total
Counts records how many times a Relay Output channel has been used. In general, each relay output channel
can be used an average of 100,000 times. Users can monitor these counts to see when the module should be
replaced, or to switch to a different channel if the total count approaches the upper limit. Relay Current
Counts can be reset to zero to record the usage of the external device by monitoring the counts. For example,
if RLY-0 is connected to an external relay control board, you can monitor the current counts to see when to
replace the external relay component in advance before it fails. Last Reset Time records the time when Current
Counts was reset. Both Relay Total Counts and Relay Current Counts will be saved when there is a power failure.
The Last Reset Time will be saved only when the user manually presses the Reset to Zero button.