ioLogik Active Ethernet I/O Family User’s Manual Initial Setup
2-6
Installing the System Power Module
The system power expansion module is designed to provide extra power when additional I/O
expansion modules are connected. Each ioLogik E4200 can provide 1.5A @ 5 VDC. If you require
more power for your installed I/O modules, you will need to use an M-7001 module. However,
please note that the M-7001 can only provide 1A @ 5 VDC.
...................
150 mA
150 mA
150 mA
150 mA
150 mA
150 mA
150 mA
150 mA
200 mA Supports 1000 mA
200 mA
200 mA
200 mA
200 mA
Total: 1400 mA
Total: 1000 mA
200 mA
Supports 1000 mA
Supports 1000 mA
ATTENTION
When the total current consumption for connected I/O modules exceeds 1.5A, an M-7001 power
expansion module is required.
The following table can be used to calculate if an extra power expansion module is needed. In
Program Files Æ MOXA Æ IO Server Æ HELP, click on Power Consumption Spreadsheet.
The spreadsheet requires Microsoft Excel to operate. Once you enter the I/O module quantity, you
will know how many power expansion modules are required.
When extra power expansion modules are installed, restart the system in the following sequence
to ensure a proper start-up.
Power Off Sequence
1. Unplug the network adaptors removable terminal block.
2. Unplug the expansion module’s removable terminal block.
Power Up Sequence
1. Plug in the power expansion module’s removable terminal block.
2. Plug in the network adaptors removable terminal block.